What does a UPS do?
Is your business at risk from power failure?

 
Union Jack Flag
 GB
AEC for all your Power requirements - call cetnre rep image

Call our sales team to
discuss your requirements
FREE PHONE

0800 136 993
International customers
Click here for our
contact number

AEC Homepage
AEC and UPS News and press releases
UPS Systems & Solutions
Reasons you should UPS back up power
UPS Service and Maintenance
AEC Diesel Powered Generators
AEC Career opportunities
Getting in touch with AEC
AEC UK montage banner
AEC > Why get a UPS
UPS Information - What does a UPS do

WHAT DOES A UPS DO?

Introduction:

Figure 3:1 UPS System Installation 

An Uninterrupted Power Supply or UPS system is employed to protect the equipment between the mains supply and the electrical load, which may be critical from abnormalities and interruptions in the power supply including mains failure. These solid-state systems or static UPS’ are connected in-between the mains supply and the load. (See above diagram).

The alternative is the rotary system which is still available and uses generator technology; however these have gradually disappeared as businesses favour the static UPS.
UPS systems are available is various static forms that are used for various reasons, however all UPS systems provide a back-up energy which is stored in a battery and utilised if the main power supply fails.

UPS Power Rating

Watts (W) or Volt Amperes (VA) are the measurements used to rate the power of electrical equipment, rarely are both used together though. VA or kVA (1kVA=1000VA) are the measurements most commonly used by UPS manufacturers in order illustrate output ratings. This rating is extremely important as it establishes the greatest load that can be supported by a specific UPS continuously when there is a power failure. If the rating is given by the manufacturer in Watts then it should be translated in to VA in order to confirm the compatibility of the UPS and the load ratings.

VA and Watts made simple

People often become perplexed by the two expressions ‘VA’ and ‘Watts,’ however it is important to understand both and their constraints and limitations, in order to match a UPS to an individual load.

Figure 3:2 VA and Watt in a Linear Circuit


As demonstrated in the top drawing of the above diagrams, the VA rating can be found by multiplying the supply voltage (V) and the current (A) drawn from the supply using the rms (root mean square) values of voltage and current in each case.

Watts (W) are calculated by multiplying the load current and the supply in the direct current (dc) circuit, this is done in an identical way to that described for VA. For example: (V × A= W.) The circuit values of VA and Watts are in some circumstances identical for instance when the supplied voltage and load current are in phase in an ac circuit which is feeding a purely resistive load. The bottom drawing of the diagram above demonstrates this.

Figure 3:3 VA and Watt in a Non-Linear Circuit

More often than not the equipments attached to an alternating current (ac) circuit are not linear. Conventional ac loads are inductive in character; this often causes the equipment to be behind the practical voltage amount by a total relative to that of the equipments reactance. The diagram above (Figure 3.3) clearly illustrates and gives example of this.

Observe in the illustration above that the Volt Ampere rating is the same as that in the previous diagram. This is due to the fact that root mean square (rms) values of voltage and waveforms are not affected by the relative phase shift. Additionally in both instances given in this explanation the current drawn from the supply is identical. Nevertheless the bottom illustration in figure 3.3 presents a declining 960W in Watts’s rating, this was previously at a figure of 1200W thus specifically the equipment is dissolving far less Watts in comparison to VA, which stays the same.

The decreased wattage is a result of the phase connection involving the current waveforms and the voltage; this is because a negative value is created by the product of V × A, as the limits are of dissimilar polarities. This is again demonstrated in Fig 3.3.

Negative power trips in the illustration are symbolising what is known as wasted power, this is power that is not dispersed in a functional way from the operating load. This wasted power is a result of and comparative to the combined load’s reactance, this is why it is occasionally mentioned as reactive waste also.

(pf) Power Factor

This can be described in simple terns as the connection between real and relative power in a alternating current (ac) circuit. It is also the ratio of Watts to Volt Ampere.
Power Factor (pf)  = Watts
 
VA

By working out the cosine of the Phase angle between the current waveforms and voltage the power factor can be easily established.
E.g. As shown in figure 3.3 in which the phase angle is 36° the load power dispersion can be worked out using the following method:

Watts = VA × cos36 = 1200 × 0.8
Watts = 960

Obviously, if there are two loads each sharing an identical wattage ratting but with different (pf) power factor’s and they are both connected to the same supply of power, the load which has the higher pf is going to take out a lesser amount of current from the shared supply as its partner load.
It is routine that a Uniterutped Power Supply is often referred to in relation to its output VA (kVA) rating. It is standard to presume a number of 0.8 in the case that there is no given output power factor on a UPS. An example illustrating this is: If a UPS is 1kVA and has a maximum power rating of 800W, 0.8 is the outcome. Also under these conditions neither of these given values should be exceeded by the total load.
Measures are taken from time to time in order to advance the complete power factor and bring it closer to harmony, this is usually in situations where large or highly reactive loads are concerned. This process is commonly known as, ‘power factor correction’ and it is in the main part accomplished by putting in a capacitive load in addition to the load equipment to reduce the complete circuit reactance.

What Uninterruptible Power Supplies are available to you

There is an extensive assortment of different UPS modules currently on the market, options range from the extremely compact desktop models that are now available up to vast units that hundreds of kVA . The systems power rating can now easily be increased to way over a thousand kVA, this is achievable when some manufacturers create their USP with the capability to be paralleled with other units. For example 2 or 3 MVA units are doable.

Desktop Units

Figure 3:4 Desktop UPS Models

Micro Models- maximum of 250VA

Micro systems in this low power range are purpose-built in order to supply and protect only a single PC. These are usually accommodated in a mini-tower box, which is around only half the size of an average PC system unit. Because of the micro models small dimensions and lightness in weight it can be considered to be transportable. It should be connected to a mains power supply outlet, for example in the UK a three-pin 13A, wall socket. Units at a power level below 250V offer a solitary point solution to a specific need and include on-line, off-line and interactive designs.
On the back on most UPS is a IEC, which is a standard mains connector that is protected by a fuse or circuit breaker, this should usually be connected to the load equipment.
Batteries for UPS units of such a low power level are typically integrated into the body of the unit; this means that it is very improbable that additional battery cabinets will be available as an extra.

Micro models are indented to be located nearby the load user, due to this factor it is not normally required that a remote alarm facility be provided to alert the user of the machine status of operation. Though, today’s needs may require that an automatic control interface be installed between the UPS and the personal computer.

Mini-models: VA of between 500-2000VA

Mini UPS models are in numerous areas very comparable to the micro units just mentioned. Both are intended to be used in offices and both are small and light enough to be deemed portable. The lager power rating of the mini UPS makes it appropriate for supplying not only a personal computer but its connecting equipment such as printer, web-cam, scanner and so on.
Like the micro systems these are designed to be plugged into a 13A three-pin socket and again can include on and off line and interactive designs.

On the back on most UPS is a IEC, which is a standard mains connector that is protected by a fuse or circuit breaker, this should usually be connected to the load equipment. However unlike the previous machine there is likely to be some additional supply outlets for small items of load equipment E.g. printers.
Again at this current power rating the batteries are likely to be integrated into the design f the UPS box, some units however may be capable of connecting supplementary batteries this would be enclosed in an additional purpose-built battery box, this would then increase the overall back-up time of the batteries. The charger for the external batteries will still be sufficient in providing the power needed to re-charge any additional batteries. On the other hand in extreme situation an external charger system may be required and thus will also need to be connected to the main power supply.
Mini models are indented to be located nearby the load user, due to this factor it is not normally required that a remote alarm facility be provided to alert the user of the machine status of operation. Depending on whether the load is critical or not, this system may often require SNMP or automatic shutdown.

About Systems between 3-20kVA (medium sized)

Figure 3:5 Medium Sized Systems

These medium sized UPS are intended to supply much more than the desktop units and are capable of supplying more than a single point power provision. These UPS are often used to power loads such as office networks and communication centres.
The medium sized model is not to be viewed as a portable machine like the two precious UPS, as they are designed to be constantly wired via a switchgear of medium power to the mains power supply, this may also need external input overload protection. Some of the biggest models in this medium range could require three-phase output as some may also produce a three-phase output.

As this is quite an extensive power range the issue of batteries changes from one end to another. At the low end of the scope the explanation about batteries concerning desktop UPS is still what to go by. However in the upper end of this range for example from 15-20 kVA batteries may be housed in an additional cabinet which is to be located adjacent to the UPS unit. These are usually attractive to the eye as many manufacturers produce a matching US and battery cabinet that fits well into most offices.
At the bottom end of the power ranger the UPS can be connected to a three-pin 13A socket similar to the desktop UPS units. In contrast to this the most powerful pf UPS in this range are designed to be hard wired to distribution busbars which will be fitting inside the cabinet provided, alternatively a purpose built distribution system can be connected through the UPS output.

About 30-400kVA High power systems

Figure 3:  Large Sized Systems
Figure 3.6 large systems

 

Systems with a high power rating are capable for proving power to large data centres, however they are not usually appropriate for use in an average office environment as they do create high noise levels while in operation, this is due to the cooling fan which is essential to lager and high-powered loads. As a result such UPS unit are generally stored in a out-of-the-way location. Their output will typically be connected to a very large number of loads, which will use a devoted power supply, this must hold an external switchgear and protective device.

These highly power system are almost always use for online design and always three-phase input and output.
Unlike the prior equipment the batteries will not be housed inside the UPS box. Depending on the required back-time they are to be stored in separate box(s) neighbouring the UPS unit or in the circumstances of an extremely large system put in a devoted battery room and rack-mounted.

A 12 pulse rectifier is in use by some of the largest UPS models in order to decrease the quantity of main inference such harmonics, these are created inside the Uninterrupted Power Supply entering the utility mains supply. With the employment of a 12-pulse rectifier a separate box is often needed to accommodate it, it is essential that it is located next to the UPS.
A generator may also be added to the systems designs with the intention that it back up the load when there is a utility mains failure. There stand-by generators must be self-starting and also must be able to maintain a clean and reliable power supply with the UPS on full load. For more information see the: About generators section.

As this UPS is likely to be located in an isolated purpose-built room a remote alarm a necessary, the majority models in this power rating range will come with this remote alarm as a standard feature.

AEC Uninterruptible Power Supply Products

T1 Series 500VA - 1kVA UPS | T2 Series 1kVA - 3kVA UPS | T3 Series 1kVA -10kVA UPS | T3R Series 1kVA - 3kVA UPS | T4 Series 10kVA - 20kVA UPS | T6 Series 10kVA - 300kVA UPS | T6Compact+ Series 10kVA - 40kVA UPS | T7 Series 10kVA - 2.6mVA UPS | Power Station Range 1kVA - 3kVA UPS | Diesel Generators